Verrolec Mez Slide On Flange
Specification
uVerrolec Mez Product Detail
 
Application
The slide on flange system is used by sheet metal contractors to join together air conditioning, ventilation or extract ductwork. Unlike angle iron, which involves drilling the fixing holes and connecting with nuts and bolts, the contractor simply cuts the flange to the ductwork dimensions, fits purpose made corner pieces to form a frame, and fits this onto either end of the ductwork section by means of spot welding or riveting. The ductwork is then bolted together with a gasket between the flanges to make the joint airtight. This allows the completed ductwork system to transfer or extract air to the required location

Features
Provides for rapid assembly of cross joints Choice of material types and gauges to suit specifications and requirements
Permanently flexible non toxic sealant injected
into the profile during manufacture
Tested and certified by BSRIA in accordance with the HVCA test procedures DW/TM1
Available in standard Euro sizes of 20mm,
30mm and 40mm
Suitable for HVCA specification Joint Ratings up to J6 and pressure classes A,B and C.
Fully conforms to UK,HVCA specification
DW144
Full range of accessories to suit all sizes of
flange
Verrolec Mez Profile

During the manufacturing process air tightness is
ensured by the inclusion of non-toxic sealant.


Part Numbers

20mm profile -ref 120L +224,225 or 226 corners

30mm profile -ref 130L +223 or 236 corners

40mm profile -ref 141 +245 corners
 
Design Specification
All rectangular ductwork cross joints shall be the Verrolec Mez slide on flange type complete with integral
permanently flexible non toxic sealant,consisting of a Galvanised MS profile and EZP corner pieces.The
appropriate size of flange shall be fitted to the ductwork as covered by the construction tables 2 to 4 of
specification DW144.Shall be independently tested to the procedures of BSRIA in accordance with HVCA
specification DW/TM1 and as manufactured by Doby Verrolec.The flanges shall be fitted to the ductwork and assembled on site with the appropriate gasket all to the manufacturers instructions.


DW/TM1 TEST RESULTS
Flange Corner J2 J3 J4 J5 J6
120L 224        
120L 225        
120L 226        
130L 233      
130L 236      
141 245       *
 
*when used with central Tie Bar
As tested by BSRIA in accordance with HVCA specification DW/TM1 test procedures